KNX IP BAOS 771
Interface between EIB/KNX-Bus and Ethernet
KNXnet/IP Tunnelling & Object-Server
With JSON Web Services
![]() |
| Fig. KNX IP BAOS 771 |
Introduction
The KNX IP BAOS 771 is one of the successors to the well-tried KNX IP BAOS 770. The KNX IP BAOS 771 offers an improved BAOS protocol and supports Web Services in Java Script Object Notation (JSON). In addition, the device enables up to 5 Tunneling (KNXnet/IP) connections and up to 10 Object Server connections simultaneously.
Existing software for a BAOS 770 must be adjusted for use with a BAOS 771. The Migration Guide contains detailed information.
Application area
The KNX IP BAOS 771 is used as interface to connect to KNX/EIB both on telegram level (KNXnet/IP Tunneling) and on data-point level (KNX Application Layer). BAOS stands for "Bus Access and Object Server". This device can be used with ETS as a programming interface. As ObjectServer the device supports up to 250 data points. It is possible to connect to KNX/EIB-Bus (telegrams) as well as to data points (communication objects) from everywhere via LAN.
Connection over the internet is possible, too. The IP settings as well as the data points can be configured with ETS software. The device requires an external power supply or can alternatively be powered via Power-over-Ethernet (IEEE 802.3af) directly from the switch.
Database
Information about the database can be found in the manual
kdrive BAOS SDK
For quick and easy integration of BAOS services in your own projects there are two free SDKs available. First, the kdrive BAOS Binary SDK, a C + + implementation of the BAOS Binary Protocol. The following systems are supported:
- Windows
- Linux
- Mac OS X
- iOS
Mechanical data
- Housing: plastic
- DIN rail mounted device, width: 2 TE
Controls
- Learning key for EIB/KNX
Indicators
- Lerning LED (red)
- Signal LED (green) for EIB/KNX
- Signal LED (green) for LAN
KNX
- Device Model System B
- Max. Communication Objects: 250
- Max. Group addresses: 2000
Ethernet
- 10BaseT (10Mbit/s)
- Supported internet protocols ARP, ICMP, IGMP, UDP/IP, TCP/IP, DHCP and Auto IP
- KNXnet/IP Protocols: Core, Device Management, Tunneling
- Max. Tunneling Connections: 5
- KNX BAOS Binary Protocol V2.0
- KNX BAOS Web Services (JSON)
- Max. BAOS Connections: 10
Power supply
- External power supply 12-24V AC or 12-30V DC
- Alternative: 'Power-over-Ethernet'
- Power consumption: < 800 mW
Connectors
- EIB/KNX connector
- LAN RJ-45 socket
- Screw connector for power supply
Download
- Data sheet
- Manual device
- Manual database
- Migration Guide 770 to 771/772
- Product database for ETS
- Protocol description: KNX BAOS Binary
- Demo application KNX BAOS Binary for MS Windows®
- Protocol description: KNX BAOS Web Services
- Article: Remote Access with ETS
- Article: KNX over IP
- Free SDK: kdriveBAOS Binary-v2 (C++)
- Free SDK: kdriveBAOS Web Services (JavaScript)